Product Description
120 VAC Model with barrier strip at input and output/with wire leads at input and output (WL)
- Model: IC+130 / IC+130WL
- Rated Output (Amps): 30
- Case Dimensions (In) A x B x C: 7.75 x 4.75 x 2.35
- Mounting Flange Dimensions (In) D x E x F x G: 8.25 x 3.50 x 9.00 x 0.19
- Screw Size: #8
- Weight (lbs): 6.0
MCOV
- 120 Volt: 150 VRMS
- 240 Volt: 275 VRMS
Line Frequency: 47 – 63 Hz
Response Time:
- Normal Mode < 0.5 ns
- Common Mode < 5 ns
Operating Temperature: -40°C to +45°C at Full Load; Derate Linearly to 60% at +70ºC
Operating Humidity: 0% to 95%
Peak Surge Current Capability (8 x 20 μs):
- Line to Neutral 15,000 Amps
- Line to Ground 15,000 Amps
- Neutral to Ground 15,000 Amps
Load Surge Current Rating:
- 10 mSec 5 x Nominal
- 1 sec 3 x Nominal
- 10 sec 2 x Nominal
Packaging:
- High Impact Plastic Case
- Vacuum Impregnated Magnetics
- Epoxy Encapsulated
Frequency Response (Forward-Reverse):
- Normal Mode 100 kHz to 50 MHz – 90 dB Min
- Common Mode 5 MHz to 50 MHz – 60 dB Min
Typical Category A Ringwave (6kV,200A,100kHz)
MODEL | NORMAL | COMMON |
IC+102 / LRIC+102 | 1.0 / 0.9 | 302 / 287 |
IC+105 / LRIC+105 | 0.7 / 0.8 | 292 / 307 |
IC+107 / LRIC+107 | 0.7 / 0.7 | 302 / 293 |
IC+115 / LRIC+115 | 0.7 / 0.7 | 304 / 306 |
IC+130 / IC+202 | 0.5 / 1.1 | 306 / 536 |
IC+205 / IC+207 | 1.5 / 0.8 | 628 / 616 |
IC+215 / IC+230 | 0.6 / 0.9 | 572 / 566 |
Typical Category B Ringwave (6kV,500A,100kHz)
MODEL | NORMAL | COMMON |
IC+102 / LRIC+102 | 178 / 188 | 302 / 285 |
IC+105 / LRIC+105 | 162 / 191 | 291 / 300 |
IC+107 / LRIC+107 | 173 / 190 | 300 / 298 |
IC+115 / LRIC+115 | 153 / 149 | 307 / 309 |
IC+130 / IC+202 | 241 / 302 | 299 / 532 |
IC+205 / IC+207 | 378 / 336 | 594 / 596 |
IC+215 / IC+230 | 272 / 342 | 548 / 578 |
Note: All measurements in volts. IEEE test results with no AC applied. Normal mode–L1-N or L1-L2; Common mode–L-G, N-G or L1-G, L2-G.